WVRC-4 Installation and Operation Manual
PROGRAMMING
NOTE: The decimal point may be added and is not considered part of the four
digits
Example: To calibrate analog (metering) channel 1, enter 1, then the desired four-
digit reading.
Example: 75.00 would be seventy-five; 750.0, seven hundred and fifty while 7500
would be seventy five hundred.
NOTE: The correct value on the analog (metering) input MUST be present for
several seconds prior to entering OP/PGM mode. Once program mode is
entered, the analog (metering) inputs are locked and changes made while in
program mode will not be read. If there is no signal on the input, an error mes-
sage will be displayed.
Enter a “2” from the Analog Set-Up menu to establish alarm set points. Analog
(metering) input set points are set up using items 1 à 4, representing analog (meter-
ing) inputs one through four.
Example: If you’re reading is normally 7000 V, and you want it to alarm when the
voltage drops below 6300 (-10%) or over 7350 (+ 5%), then enter 6300/7350.